半岛体育·(中国)官方网站-bd SPORTS

Welcome to Lvneng Electricity Technology Co.,Ltd.

PVC Insulated Cable for House Wiring

PVC Insulated Nylon Sheathed Building Wire

PVC Insulated Nylon Sheathed Building Wire

    Share:

1. Standard

JB/T10261-2001: PVC Insulated and Nylon Jacketed Wires and Cables with Rated Voltages up to and including 450/750V.

2. Application

This product is used for power lines of rated voltage 450/750V and below.


3. Guide to Use

Max. conductor temperature in normal use is 70℃.


4. Code, Description and Specifications
Code Description Rated Voltage (V) No. of Cores Sectional Area (mm2)
BVN Copper conductor PVC insulation Nylon sheath cable 300/500 1 0.5~10
BVNNB Copper conductor PVC insulation Nylon sheath flat cable 300/500 2,3 0.75~10

5. Technical Particulars
1) BVN

Sectional Area

(mm2)

Conductor Class

Insulation Thickness

(mm)

Nylon Thickness

(mm)

Overall Diameter

(mm)

Approx. Weight

(kg/km)

Max. Conductor DC Resistance at 20℃

(Ω/kM)

Min. Insulation Resistance

(Ω/km)

0.5 1 0.35 0.1 1.70 6.72 36.0 0.015
0.75 1 0.35 0.1 1.87 9.11 24.5 0.012
0.75 2 0.35 0.1 2.01 9.62 24.5 0.014
1 1 0.35 0.1 2.03 11.72 18.1 0.011
1 2 0.35 0.1 2.19 12.32 18.1 0.013
1.5 1 0.4 0.1 2.4 17 12.1 0.011
1.5 2 0.4 0.1 2.6 18 12.1 0.010
2.5 1 0.4 0.1 2.8 27 7.41 0.010
2.5 2 0.4 0.1 3.0 28 7.41 0.009
4 1 0.4 0.1 3.3 41 4.61 0.0085
4 2 0.4 0.1 3.6 42 4.61 0.0077
6 1 0.5 0.1 4.0 61 3.08 0.0070
6 2 0.5 0.1 4.3 63 3.08 0.0065
10 2 0.7 0.13 5.7 108 1.83 0.0065
16 2 0.8  0.13 7.0
168 1.15 0.0028
25 2 1.0  0.15 8.7
265 0.727 0.0030
35 2 1.0  0.15 9.9
358 0.524 0.0032
50 2 1.2  0.18 11.7
488 0.387 0.0032
70 2 1.3  0.18 13.7
694 0.268 0.0032
95 2 1.3  0.18 15.6
944 0.193 0.0032
120 2 1.4  0.18 17.4
1187 0.153 0.0035
150 2 1.5  0.2 19.4
1469 0.124 0.0035
185 2 1.6  0.2 21.4
1832 0.0991 0.0045
240 2 1.6  0.2 24.1
2379 0.0754 0.0040
300 2 1.8  0.23 26.9
2984 0.0601 0.0050
400 2 1.8  0.23 38.9
3863 0.0470 0.0050

2) BVNNB

No. of Cores * Sectional Area

(mm2)

Conductor Class

Insulation Thickness

(mm)

Nylon Thickness

(mm)

Cable Dimension
(mm)
Approx. Weight
(kg/km)

Max. Conductor D.C Resistance at 20℃

(Ω/kM)

Minimum insulation resistance
Ω/km
2*0.75 1 0.35 0.1 3.7*5.5 34 24.5 0.012
2*1 1 0.35 0.1 3.8*5.7 40 18.1 0.011
2*0.15 1 0.4 0.1 4.2*6.6 53 12.1 0.011
5*2.5 1 0.4 0.1 4.8*7.6 78 7.41 0.010
2*4 1 0.4 0.1 5.3*8.5 109 4.61 0.0085
2*4 2 0.4 0.1 5.6*9.1 114 4.61 0.0077
2*6 1 0.5 0.1 6.2*10.1 158 3.08 0.0070
2*6 2 0.5 0.1 6.5*10.8 165 3.08 0.0065
2*10 2 0.7 0.13 8.1*13.8 270 1.83 0.0065
3*0.75 1 0.35 0.1 3.7*7.4 48 24.5 0.012
3*1 1 0.35 0.1 3.8*7.9 57 18.1 0.011
3*1.5 1 0.4 0.1 4.2*8.9 76 12.1 0.011
2*2.5 1 0.4 0.1 4.8*10.3 112 7.41 0.010
3*4 1 0.4 0.1 5.5*12.0 163 4.61 0.0085
3*4 2 0.4 0.1 5.8*12.9 170 4.61 0.0077
3*6 1 0.5 0.1 6.2*14.1 231 3.08 0.0070
3*6 2 0.5 0.1 6.5*15.2 240 3.08 0.0065
3*10 2 0.7 0.13 8.1*19.5 397 1.83 0.0065

Other Products

  • Non-sheathed Cables for Fixed Wiring

  • Copper and Aluminum conductor PVC Insulated Cables for Fixed Wiring

  • PVC Insulated and Sheathed Cables for Fixed Wiring

  • PVC Sheathed Flexible Cables

  • PVC Insulated Twisted Flexible Cable

  • PVC Sheathed Screened Flexible Cable

  • Flame retardant nylon jacket line